FPT Systems Approved by Factory Mutual
|
FPT Systems Approved by Factory Mutual*
Penetrants:
|
FM
Design
No.
|
FM
Assigned
Rating, (hours)
|
Products
|
Corresponding
UL System
|
Corresponding
F and T ratings
|
Type
|
Nominal Dia. (inches)
|
Schedule
|
F (hours)
|
T
(hours)
|
steel
|
1.5
|
10
|
119
|
1/2
|
E473
|
CAJ 1083
|
3
|
0
|
copper
|
2
|
M
|
conduit, EMT
|
1.5
|
10
|
steel
|
10
|
10
|
120
|
1 and 1.5
|
E473, E983
|
CAJ 1082
|
3
|
0, ½
|
pipe, conduit
|
6
|
40
|
steel, or Al flexible conduit
|
4
|
 |
121
|
2
|
E473
|
 |
 |
 |
cables
|
 |
 |
122
|
1,2,3
|
E473
|
CAJ3046
|
3
|
½, 3/4,1,2, and 3
|
steel
|
1.5
|
10
|
123
|
2
|
A107
|
CAJ1085
|
3
|
0
|
copper
|
2
|
M
|
cables,
cables in
cable tray
|
 |
 |
124
|
3
|
E473
|
CAJ5200
|
3
|
1,2, and 3
|
CAJ5201
|
2
|
CAJ5202
|
3
|
steel moving pipe
|
20
|
10
|
125
|
3
|
E424
|
CAJ1086
|
3
|
1
|
floor-floor
construction joint
|
 |
 |
126
|
3
|
A107
|
FFS0019
|
3**
|
-
|
pipes, steel, copper
conduit, steel
power cables .Cable trays with power cables
|
6
6
4
|
10
L
|
441***
442***
|
***
***
|
E473
external
seal
|
CAJ 1434
|
3
|
¾, 1½, 2
|
 |
CAJ 4061
|
3
|
2 and 3
|
* FACTORY MUTUAL FM Approval Guide® in www.approvalguide.com, or in CD For Firestop seals from Factory Mutual.
** Assembly rating,
*** FM report in preparation
FM temperature rating is based on similar fire and hose stream test as by UL, but reading is from a thermocouple placed
on the unexposed side of fire stop at 1 inch (25.4 mm) from penetration, for as long as that the temperature does not
exceed 325°F(163°C) above initial temperature, similar to T rating by UL.
FM Approval for Flammadur A77 cable coating for Group Electric Cables, listed in FM Approval (CD), May 2008, Volume 7, pg. 3.
(see A77 FM approval)
Copyright © 2008 Fire Protection Technologies, Inc. All rights reserved
|