FLAMMADUR® E292 PENETRATION SEAL
|
Flammadur® E292 is a two component polyurethane resin which is used to seal through mechanical parts in penetrations to protect them from fire within the penetration.
Flammadur® E292 is flexible flame retardant which has excellent resistance to water and, to a large extent, is resistant to usual technical oils and weak/ diluted acids and caustic solutions. It halogen free and cold hardening and contains no asbestos or harmful solvents.
Features: Product Features:
Tight seal for high water pressure can be obtained by inserting, inside E473, a layer of high polyurethane based Flammadur® E292.
Safety seal, for high pressure firestop requirements besides fire-proofing
smoke and water tightness after a fire (pressure and flood-water resistant).
Developed for the protection of expensive buildings and installations.
The FWG System excels especially in high loading capacity, mechanical stability, optimum bonding to concrete and durability.
Non Toxic: Contains no asbestos or harmful solvents. (Avoid contact with bare skin and eyes.)
Uses:
Flammadur® E292 is used as a water resistant sealing compound for cable penetrations and cabled bulkheads as well as for electrical and mechanical construction units like bus parts.
Application on ships in Geaquello System for passage through bulkheads
and decks:
For cables Flammadur® E292 is used on a deck, on the top of E950 for a depth of
10 mm (see Fig. 3b in Geaquello System, under heading of Transit Box)
For electric busway in Geaquello System, under heading Electric Busway, for a depth of 110 mm
Flammadur® E292 is flexible flame retardant which has excellent resistance
to water, contains no asbestos or harmful solvents. Avoid contact with
bare skin and eyes, for details, please consult Material Safety Data Sheet.
Non Toxic:
Contains no asbestos or harmful solvents. Avoid contact with bare skin
and eyes.
Instructions:
The hardener is contained in a small chamber that is effectively the lid of the main container.
Remove the plastic cap in the lid with a screwdriver or similar tool, and puncture the base of the lid.
Its contents, the hardener, will drain into the resin in the container.
Remove the metal clamp and the lid from the container.
Stir the compound until the mixture reaches aneven color indicating that the mixture is homogeneous.
Do not leave any of the resin in the bottom of the container.
After the resin and the hardner have been weel mixed, use immediately.
Tools and spills must be cleanedwith an organic solvent.
Apply the mixture by pouring directly from the can or with the aid of a hand pump.
No special equipment is needed.
Do not apply below 5ºC (41ºF).
Spraying:
Special spraying equipment can be used to spray a mixture of 7.25 parts
resin to one part of hardener.
Copyright © 2008 Fire Protection Technologies, Inc. All rights reserved
|