Flammadur® A77HF
CABLE COATING for GENERAL CONSTRUCTION
Summary
FLAMMADUR® A77 HF, a firestop cable coating, is an intumescent fire protection coating (an improved version of A77)
Range of application
When exposed to fire, FLAMMADUR® A77 HF expands and turns to an insulating carbon char, protecting the underlying cable against heat. It is designed to prevent the propagation of fire along cables and prevents short-circuits or sparks, even off high voltage cables, from starting fires. In the case of an external fire, damage to cables and insulation is delayed for a minimum of 30 minutes. As a result, escape routes and power supplies stay available longer. Cable fire load is significantly reduced. Smoke generated from the protected materials is < 400%/min. The coating does not affect the cables' current carrying capacity in any way.
Application
Application areas must be dry, clean and free of grease.
Surface and air temperature should be > 5°C.
Please stir well before use.
The coating can either be applied with a brush or roller or using airless spray equipment. Two coats are needed.
If required, product may be diluted with water.
The dry layer of FLAMMADUR® A77 HF should be at least 1.59 mm thick, as per Factory Mutual specification. This requires a wet layer of approximately 3 kg/m².
When exposed to humidity, e.g. in wet rooms or outdoors,
FLAMMADUR® A77 HF may be additionally treated with FLAMMADUR® V 906 protective varnish, or waterproof film or plastic covering
Allow the cable coating to dry for a minimum 24 hours at room temperature before applying varnish.
All components of the FLAMMADUR System are neutral, harmless to humans and the environment and require no special labeling.
Before exposure to fire:
|
After exposure to fire:
|