Summary of UL® Approved Flammadur® Systems
|
Copyright © 2006 Underwriters Laboratories Inc.
Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc.
Fill, Void or Cavity Materials
Acrylic Firestop Sealant Flammadur A108 for use in Joint System Nos. FF-D-1052, FW-D-1052, HW-D-0060, HW-D-0061, HW-D-0119, HW-D-0120, HW-D-0339, HW-D-1011, HW-D-1012, HW-D-1047, WW-D-1046.
Intumescent Acrylic Firestop Sealant Flammadur A109 for use in Through-Penetration Firestop System Nos. C-AJ-1475, C-AJ-1476, C-AJ-1477, C-AJ-1478, C-AJ-2444, C-AJ-3221, C-AJ-5246, C-AJ-5247, C-AJ-6034, C-AJ-8137, F-C-1109, F-C-3075, F-C-5068, W-J-1142, W-J-1143, W-J-5099, W-J-7060, W-J-8026, W-L-1317, W-L-1318, W-L-1319, W-L-1320, W-L-1321, W-L-2362, W-L-2363, W-L-3228, W-L-5199, W-L-5200, W-L-5201, W-L-5202, W-L-7103, W-L-8048.
Type E473 mortar for use in Through-Penetration Firestop System Nos. C-AJ-0109, C-AJ-1042 , C-AJ-1043, C-AJ-1082, C-AJ-1083, C-AJ-1084, C-AJ-1411, C-AJ-1412, C-AJ-1413, C-AJ-1434, C-AJ-1504, C-AJ-3028, C-AJ-3046, C-AJ-4012, C-AJ-4061, C-AJ-4068, C-AJ-5200, C-AJ-5201, C-AJ-5202, C-AJ-7029, C-AJ-7030, C-BJ-0029, C-BJ-1010, C-BJ-3008, C-BJ-3009, C-BJ-4010, W-L-1197 and W-L-5163.
Type E983 mortar for use in Through-Penetration Firestop System No. C-AJ-1082.
Type AS11 fabric for use in Through-Penetration Firestop System No. C-AJ-1086.
Type A110SP spray for use in Joint System Nos. CW-S-1018, CW-S-2063, FF-D-1068, FF-D-3009, FF-S-1035, FW-D-1063, FW-S-1021, HW-D-0422, HW-D-0423, HW-D-0424, HW-D-0425, HW-D-0426, HW-D-0427, HW-D-0428, HW-D-0429, HW-D-0430, HW-D-0431, HW-D-0432, HW-D-0433, HW-D-0434, HW-D-0435, HW-D-0436, HW-D-0437, HW-D-0438, HW-D-0439, HW-D-1061, HW-D-1062, HW-D-1063, HW-S-0078, HW-S-1017, WW-D-1058.
Type 100 WC collar for use in Through-Penetration Firestop System Nos. C-AJ-2572, W-L-2476.
Joint Systems
GENERAL
A joint system is a specific construction consisting of adjacent wall and/or floor assemblies and the materials designed to prevent the spread of fire through a linear opening between the wall and/or floor assemblies. The specifications for materials in a joint system and the assembly of the materials are details which directly relate to the established ratings. Information concerning these details is described in the individual systems. The hourly ratings apply only to the complete systems. Individual components are designated for use in a specific system to achieve specified ratings. The individual components are not assigned ratings and are not intended to be interchanged between systems. Additionally, the substitution or elimination of components required in a system should not be made unless specifically permitted in the individual system or in these general guidelines.
The basic standard used to investigate products in this category is ANSI/UL 2079, "Tests for Fire Resistance of Building Joint Systems".
ANSI/UL 2079 defines four types of joint systems: floor-to-floor, wall-to-wall, floor-to-wall and head-of-wall. In addition, bottom-of-wall joint systems have been investigated using the general methods and conditions of acceptance specified for the four defined types of joint systems.
All joint systems described herein have been investigated with a minimum positive furnace pressure differential of 0.01 in. of water maintained at a distance of 12 in. below horizontal test assemblies and at the mid-height of vertical test assemblies.
ANSI/UL 2079 requires joint systems with movement capabilities to be cycled through the intended range of movement prior to the fire test. The movement cycling is intended to demonstrate the compatibility between the individual components of the joint system and the fire resistive assembly. Joint systems are required to be cycled through the intended movement range 500 or 100 complete movement cycles at a minimum rate of 1, 10 or 30 cycles per minute prior to the fire test.
Joint systems with movement capabilities are noted through the appearance of a Class I, II and/or III designation included as part of the heading information. The definitions of the movement class designations are as follows:
Movement
Class
|
Min No.
of Cycles
|
Min Cycling Rate
(cycles per min)
|
Class I
|
500
|
1
|
Class II
|
500
|
10
|
Class III
|
100
|
30
|
Each joint system with movement capabilities specifies a nominal joint width and the movement capabilities, expressed in either a numerical value or as a percent of the nominal joint width. When the compression or extension movement capabilities are expressed as a percent, the minimum and maximum joint widths that the joint system can accommodate are calculated as follows:
Wmin = Wnom[1 - (% Exp / 100)]
Where:
Wmin = Minimum Joint Width, In.
Wnom = Nominal Joint Width, In.
% Exp = Movement Capability in Compression Direction, Percent
and
Wmax = Wnom[1 + (% Comp / 100)]
Where:
Wmax = Maximum Joint Width, In.
Wnom = Nominal Joint Width, In.
% Comp = Movement Capability in Extension Direction, Percent
When the shear movement capabilities are expressed as a percent, the shear movement capabilities in inches that the joint system can accommodate are calculated as follows:
Shear = Wnom(% Shear / 100)]
Where:
Shear = Shear Movement, In.
Wnom = Nominal Joint Width, In.
% Shear = Shear Movement, Percent
All joint systems have been tested at their maximum joint width and maximum shear capabilities .
Joint systems intended to be load bearing are evaluated with respect to the ability to carry the load during the fire test. The load carrying capacity of such joints is noted in the individual joint system.
The Classification of joint systems contemplate installation in heated and air conditioned environments unless stated otherwise in the description of the system.
The conditions of acceptance in ANSI/UL 2079 provides criteria for an assembly rating and an optional L rating. The L rating criteria determines the amount of air leakage, in cubic feet per minute per linear foot of joint opening (CFM/LIN Ft), through the joint system at ambient and/or 400°F air temperature at an air pressure differential of 0.30 in. W.C. The L ratings are intended to assist Authorities Having Jurisdiction, and others, in determining the suitability of joint systems for the protection of openings in floors and smoke barriers for the purpose of restricting the movement of smoke in accordance with NFPA 101, "Code for Safety to Life from Fire in Buildings and Structures."
Materials used in the joint systems are intended to be installed in accordance with the manufacturer's instructions provided with the material. The structural integrity of the floor or wall assembly has not been evaluated as a result of the openings.
When the joint system specifies the insulation material is to be compressed prior to installation into the joint, the uncompressed thickness necessary can be calculated as follows:
Tuncomp = (Wnom x 100) / (100 - Icomp)
Where:
Tuncomp = Uncompressed Thickness Necessary, In.
Wnom = Nominal (Installed) Joint Width, In.
Icomp = Insulation Compression Percentage Specified in System
Unless otherwise indicated in the systems, the ratings for joint systems installed in walls apply when either face of the wall is exposed to fire. The ratings for joint systems installed in a floor apply when the underside or ceiling surface is exposed to fire.
Volume 1 of the Fire Resistance Directory covers the hourly fire resistance rating of the floor and wall assemblies in which, or between which, the joint system is installed. Where the individual joint system references back to fire resistance designs contained in Volume 1 of the Fire Resistance Directory, all construction details of the individual design must be followed. In addition, all details relative to the construction of the wall or floor assembly contained in the individual joint system must be followed. Where the construction details shown in the fire resistance design and the joint system differ, such as in stud size and spacing, fastener spacing, etc., the most restrictive construction details prevail.
Floor-to-floor and floor-to-wall joint systems that specify installation in concrete floors may include installation in floors consisting of fluted or corrugated steel deck topped with structural concrete, provided that (1) the concrete topping thickness measured above the top plane of the steel deck is equal to or greater than the minimum concrete thickness specified in the joint system, and (2) the joint system does not require any portion of the forming material or fill material to extend below the bottom plane of the floor.
The surface flammability and smoke development characteristics of Classified materials used in joint systems are measured by the test method in ANSI/UL 723 (ASTM E84 and NFPA 255), "Test for Surface Burning Characteristics of Building Materials". The flame spread index of these materials is less than 200 and the smoke developed index is less than 450. Surface Burning Characteristics Classifications are contained in the Building Materials Directory.
Authorities Having Jurisdiction should be consulted as to the particular requirements covering the installation and use of these Classified systems. Those materials identified by an (*) in the system description text are eligible to be produced under the Follow-Up Service Program of Underwriters Laboratories Inc. The Classification Mark of UL on the product is the only method provided by UL to identify products that have been produced under its Classification and Follow-Up Service.
NUMBERING SYSTEM
The systems are identified in this category by an alpha-alphanumeric identification system. The alpha components identify the type of joint system and whether the joint system has movement capabilities. The numeric components identify the nominal joint width. In the case of head of wall joint systems, the width of the joint does not include the voids created under the crests of metal deck floor or roof systems.
The first two alpha characters identify the type of joint system as follows:
Alpha Characters
|
Description of Joint System
|
FF
|
Floor-to-Floor
|
WW
|
Wall-to-Wall
|
FW
|
Floor-to-Wall
|
HW
|
Head-of-Wall
|
BW
|
Bottom-of-Wall
|
CG
|
Wall-to-Wall Joints Intended for use as Corner Guards
|
The third alpha character is either S or D. The S signifies joint systems that do not have movement capabilities. This D signifies joint systems that do have movement capabilities.
The numeric component uses sequential numbers to identify the nominal width of the joint systems. The significance of the number used is:
No. Range
|
Nom Joint Width
|
0000 - 0999
|
Less than or equal to 2 in.
|
1000 - 1999
|
Greater than 2 in. and less than or equal to 6 in.
|
2000 - 2999
|
Greater than 6 in. and less than or equal to 12 in.
|
3000 - 3999
|
Greater than 12 in. and less than or equal to 24 in.
|
4000 - 4999
|
Greater than 24 in.
|
ADDITIONAL INFORMATION
For additional information, see Fire Resistance Ratings (CCN+and+GUIDEINFO"BXRH).
Last Updated on 2002-12-06
|
Questions?
|
Notice of Disclaimer
|
Page Top
|
Copyright © 2006 Underwriters Laboratories Inc.®
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2006 Underwriters Laboratories Inc.®"
|